Q: Will the leakage current to ground adversely affect my power system?

A: With a typical 3-phase 480 system, the maximum ground leakage current is less than 0.455mA. Under nominal conditions, this current would be much lower. It takes 0.060mA to operate the R-3W flashing circuit. A leakage current this small would have negligible effect on your power system.